Temporary works & site · Formwork & falsework

Concrete formwork pressure (CIRIA R108) calculator

Lateral pressure of fresh concrete on wall or column formwork from the rate of rise, temperature, form height and mix (CIRIA R108), capped at full hydrostatic, with the tie load for a given tie grid and the form-face pressure envelope drawn to scale.

Standard: CIRIA Report 108 · AS 3610.1 formwork for concrete (design pressure) · tie loads

Open the live calculator → All temporary works & site calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
ElementWall (C1 = 1.0)
Form height4m
Vertical pour height4m
Rate of rise2m/h
Concrete temperature20°C
Mix coefficient C2 (0.3 OPC … 0.6 with retarder/blends)0.45
Concrete density25kN/m³
Tie spacing (each way)0.9m

Worked example — results

ResultValueUnit
Temperature coefficient K1.000
CIRIA pressure53.4kPa
Hydrostatic limit Dc·h100.0kPa
Design pressure Pmax53.4kPa
Depth to Pmax2.14m
Tie load43.3kN
P = 53.4 kPahydrostatic 1004 mhmax 2.14 mties @ 0.9 m: 43 kNFormwork section & design pressureScale 1:50 at 180 mm print width01 m
Diagram for the worked example

Method, formulas and assumptions

Related temporary works & site calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.