Timber · Bracing & floors

Bracing walls: racking force and capacity calculator

Wind racking force on a house or shed in one direction from the area of the elevation (half the wall height plus the roof above) times the lateral wind pressure for the wind classification. Two bracing types with their lengths give the total capacity; the tool checks the capacity, reports the shortfall in metres of the stronger type, the tie-down force at each panel end and the maximum spacing between bracing walls.

Standard: AS 1684.2/.3 Section 8 bracing method: racking force = area of elevation × lateral wind pressure; bracing-unit capacities by type (Table 8.18, indicative values) · spacing of bracing walls ≤ 9 m

Open the live calculator → All timber calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
Building dimension facing the wind14m
Wall height (top plate)2.7m
Roof height above the top plate1.8m
Lateral wind pressure on the elevation (AS 1684 tables)0.9kPa
Bracing type 1(h) Plywood, with end tie-down rods
Length of type 16m
Bracing type 2(c) Two diagonal metal straps (tensioned)
Length of type 24.8m
Largest spacing between bracing walls8.5m

Worked example — results

ResultValueUnit
Area of elevation44.1m²
Racking force39.7kN
Capacity type 1 (6 kN/m × 6 m)36.0kN
Capacity type 2 (1.5 kN/m × 4.8 m)7.2kN
Total bracing capacity43.2kN
Extra length of the stronger type needed0.00m
Tie-down per panel end (strongest type)16.2kN
area of elevation 44.1 m² (shaded + roof)
Diagram for the worked example

Method, formulas and assumptions

Related timber calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.