Glulam / LVL beam (AS 1720.1) calculator
Simply supported glulam or LVL beam carrying a floor or roof strip. Design capacities φk1k12·f′b·Z and φk1·f′s·As for the two load durations (1.35G with k1 = 0.57, 1.2G + 1.5Q with the chosen k1), lateral stability from the restraint spacing (k12 via S1 and ρb), long-term deflection with creep factor j2, and the floor natural frequency.
Standard: AS 1720.1-2010 Cl 3.2 bending (k1, k12 stability), Cl 3.2.5 shear, Cl 2.4.1 creep j2 · AS/NZS 1328 glulam grades
Inputs in the worked example
The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.
| Input | Value | Unit |
|---|---|---|
| Grade | GL17 | |
| Breadth b | 135 | mm |
| Depth d | 540 | mm |
| Span | 7.2 | m |
| Tributary width | 3 | m |
| Dead load (excl. self-weight) | 1 | kPa |
| Live load | 2 | kPa |
| k1 for G + Q (5 months floor = 0.8) | 0.8 | |
| Spacing of lateral restraints to the compression edge | 1.2 | m |
| Capacity factor φ | 0.85 | |
| Creep factor j2 (seasoned) | 2 | |
| Deflection limit L / | 300 |
Worked example — results
| Result | Value | Unit |
|---|---|---|
| Properties f′b / f′s / E | 42 / 3.7 / 16700 | MPa |
| Self-weight | 0.400 | kN/m |
| S1 / ρb / k12 | 7.45 / 0.885 / 1.000 | |
| 1.35G: M* / φMd (k1 0.57) | 29.7 / 133.5 | kNm |
| 1.2G + 1.5Q: M* / φMd (k1 0.8) | 84.8 / 187.4 | kNm |
| 1.2G + 1.5Q: V* / φVd | 47.1 / 122.3 | kN |
| Deflection: dead (short) / live | 4.0 / 7.1 | mm |
| Long-term j2(G + 0.4Q) + 0.6Q | 18.0 (L/400) | mm |
| Natural frequency (dead load) | 8.9 | Hz |
- ✓ Bending, permanent (1.35G) — 22 %
- ✓ Bending, G + Q — 45 %
- ✓ Shear
- ✓ Long-term deflection ≤ L/300
- ✓ Live-load deflection ≤ L/360
- ✓ Frequency ≥ 8 Hz (floors)
Method, formulas and assumptions
- φMd = φ·k1·k4·k6·k9·k12·f′b·Z with k4 = k6 = k9 = 1 (dry, normal temperature); shear φ·k1·f′s·As with As = 2bd/3.
- k12 (Cl 3.2.4): S1 = 1.25(d/b)(Lay/d)^½ for discrete restraint of the compression edge; ρb = 14.71(E/f′b)^−0.48·r^−0.061; k12 = 1 (ρbS1 ≤ 10), 1.5 − 0.05ρbS1 (≤ 20), 200/(ρbS1)².
- Grade properties are typical (AS/NZS 1328 glulam, proprietary LVL): use the manufacturer's published values for design.
- Floor vibration: f = (π/2L²)√(EI/m) under the permanent load; ≥ 8 Hz is a common target for timber floors.
Related timber calculators
- Timber beam / joist (AS 1720.1) — Bending and shear capacity with load-duration factor k1 and long-term deflection with j2 for MGP, F-grade…
- Flitch beam (timber with a steel plate) — Two timber members bolted either side of a steel plate. Moments share in proportion to EI; each material is…
- Timber bearing perpendicular to grain — Bearing capacity with the bearing-length factor k7.
- Timber beam shear — Shear capacity with As = (2/3) b d for rectangular sections.
- Timber pile (structural + geotechnical) — Compression capacity of a tapered round timber pile at ground level (with stability factor k12) and at the…
- Timber wall stud: axial load and wind — Load-bearing stud carrying the roof or floor load and face wind pressure. Slenderness about the major axis…
For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.