Foundations · Pile testing & NDT

Pile set-up from restrike testing calculator

Back-calculates the set-up factor A from end-of-drive and restrike capacities, then extrapolates the capacity at a design age.

Standard: Skov & Denver (1988): Q(t)/Q0 = 1 + A·log10(t/t0)

Open the live calculator → All foundations calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
Capacity at end of driving (EOD)1500kN
Capacity at restrike2360kN
Restrike time after driving14days
Reference time t0 (≈1 day clay, 0.5 day sand)1days
Design age100days
Design action E*1200kN
φg0.65

Worked example — results

ResultValueUnit
Set-up factor A = (Qr/Q0 − 1)/log10(tr/t0)0.500
Capacity at design age3,001kN
φg × restrike capacity (no extrapolated gain)1,534kN
00.5limit 1.0φg × restrike capacity ≥ E*0.78 PASS
Diagram for the worked example

Method, formulas and assumptions

Related foundations calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.