Foundations · Pile testing & NDT

Bi-directional (O-cell) test: equivalent top-down capacity calculator

Fits hyperbolas to two points on the upward (shaft) and downward (base) curves and adds them at a common displacement to give the equivalent head capacity.

Standard: ASTM D8169 · hyperbolic curve fitting (Chin–Kondner) · rigid-pile equivalent curve

Open the live calculator → All foundations calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
Upward: cell load point 11500kN
Upward displacement at point 11.5mm
Upward: cell load point 23000kN
Upward displacement at point 212mm
Downward: cell load point 11500kN
Downward displacement at point 110mm
Downward: cell load point 23000kN
Downward displacement at point 240mm
Buoyant weight of pile above the cell150kN
Reference settlement for capacity25mm
Design action E*2500kN
φg0.75

Worked example — results

ResultValueUnit
Shaft b = Δ(s/Q)/Δs0.0001/kN
Shaft a0.001mm/kN
Base b0.0001/kN
Base a0.004mm/kN
Net shaft resistance at sref3,091kN
Base resistance at sref2,500kN
Equivalent head load Qs + Qb5,591kN
Shaft asymptote 1/b − W3,350kN
Base asymptote 1/b4,500kN
Design capacity φg·Qe4,193kN
Check: largest measured displacement40.00mm
01e32e33e34e35e36e3010203040Load (kN)Displacement (mm)
Diagram for the worked example

Method, formulas and assumptions

Related foundations calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.