Foundations · Pile testing & NDT

Impulse response (mobility) test: length and impedance calculator

Length from the spacing of resonant peaks in the mobility spectrum, and the equivalent diameter from the measured characteristic mobility.

Standard: ASTM D5882 transient response · Δf = c/2L · N = 1/(ρcA)

Open the live calculator → All foundations calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
Wave speed c3900m/s
Concrete density ρ2400kg/m³
Nominal diameter0.6m
Record length12m
Resonant peak spacing Δf162.5Hz
Measured mean mobility N0.39×10⁻⁶ m/s/N

Worked example — results

ResultValueUnit
Nominal area0.283m²
Theoretical mobility 1/(ρcA)0.378×10⁻⁶ m/s/N
Equivalent diameter √(4/(πρcN))0.591m
Check: De / D0.984
Check: |length deviation|0.000%
Length L = c/(2Δf)12.00m
020040060080000.20.40.60.811.21.41.6Frequency (Hz)Mobility (×10⁻⁶ m/s/N)N measured1/(ρcA)
Diagram for the worked example

Method, formulas and assumptions

Related foundations calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.