Masonry · Lateral load & panels
Unreinforced masonry: vertical bending calculator
Vertical bending capacity per metre using the flexural tensile strength f′mt plus the precompression, against a wind/lateral UDL.
Standard: AS 3700 Cl 7.4.2
Inputs in the worked example
The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.
| Input | Value | Unit |
|---|---|---|
| Wall thickness | 110 | mm |
| Flexural tensile strength f′mt | 0.2 | MPa |
| Design compressive stress at section | 0.1 | MPa |
| Span (vertical) | 2.4 | m |
| Lateral pressure | 0.6 | kPa |
| Support | Simple top & bottom (wH²/8) |
Worked example — results
| Result | Value | Unit |
|---|---|---|
| Zd = t²/6 per m | 2,016,667 | mm³/m |
| Mcv = φ f′mt Zd + fd Zd (≤ 3φf′mt Zd) | 0.444 | kNm/m |
| M* | 0.432 | kNm/m |
- ✓ M* ≤ Mcv
Method, formulas and assumptions
- Zd = t²/6 per m = 110^2/6*1000 = 2.017e+6 mm³/m
- Mcv = φ f′mt Zd + fd Zd (≤ 3φf′mt Zd) = MIN(0.6*0.2*2.017e+6+0.1*2.017e+6,3*0.6*0.2*2.017e+6)/1E6 = 0.44367 kNm/m
- M* = 0.6*2.4^2/IF(1=1,8,2) = 0.432 kNm/m
Related masonry calculators
- Masonry panel in two-way bending — Unreinforced masonry panel supported on four sides, or three sides with the top free, under uniform face…
- Cavity wall: load sharing and wall ties — Two masonry leaves joined by ties across the cavity, spanning vertically between supports. Wind on the outer…
- Unreinforced masonry wall: compression — Characteristic masonry strength from the unit strength, slenderness Srs and reduction ks, design compressive…
- Reinforced masonry shear wall (AS 3700) — Core-filled reinforced blockwork wall racking under an in-plane horizontal force. Shear capacity Vd =…
- Reinforced masonry wall: out-of-plane bending — Bending capacity per metre of a reinforced core-filled block wall, with the steel ratio limit.
- Masonry wall with an opening: piers, lintel, bearing — Unreinforced masonry wall with a window or door opening carrying a line load from the floor or roof. Load to…
For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.