Ground engineering · Groundwater & dewatering

Dewatering: drawdown, pumping rate and neighbour settlement calculator

Excavation treated as an equivalent large-diameter well in an unconfined or confined aquifer: radius of influence (Sichardt), pumping rate for the required drawdown at the excavation, drawdown with distance, and the consolidation settlement of a compressible layer under neighbouring buildings caused by the increase in effective stress. Checks the angular distortion across the nearest building.

Standard: Dupuit–Thiem · Sichardt radius of influence · CIRIA C750 groundwater control · Burland & Wroth damage criteria

Open the live calculator → All ground engineering calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
Excavation length40m
Excavation width25m
AquiferUnconfined
Permeability k0.0001m/s
Saturated thickness / head above aquifer base15m
Confined aquifer thickness8m
Drawdown required at the excavation6m
Radius of influence (0 = Sichardt 3000 s √k)0m
Yield per well / wellpoint header4L/s
Distance to near side of the neighbouring building8m
Distance to far side20m
Compressible layer thickness under the building4m
Coefficient of volume compressibility mv0.31/MPa
Tolerable angular distortion (1 in …)500

Worked example — results

ResultValueUnit
Equivalent well radius17.8m
Radius of influence R0180m
Pumping rate Q19.6L/s
Wells / headers at the stated yield5
Drawdown at the near side of the building4.80m
Settlement near / far side56.5 / 43.5mm
Angular distortion1 in 923
0204060801001201401600123456Distance from the excavation (m)Drawdown (m)building0204060801001201401600204060Distance (m)Settlement (mm)
Diagram for the worked example

Method, formulas and assumptions

Related ground engineering calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.