Foundations · Pile capacity

Driven pile capacity from SPT (Meyerhof) calculator

Shaft friction layer by layer from SPT N and base resistance from N at the toe with the embedment into the bearing layer (last row), then φg·Rug against the design action.

Standard: Meyerhof (1976): qb = 40N·Lb/D ≤ 400N kPa, fs = 2N̄ (displacement) or 1N̄ (small displacement) ≤ 100 kPa · AS 2159 φg

Open the live calculator → All foundations calculators

Inputs in the worked example

The live calculator starts with these values; change any of them and every result, check and diagram updates instantly.

InputValueUnit
Pile size (square side or diameter)0.4m
SectionSquare
Pile typeDisplacement (precast, closed tube)
Design action E*900kN
φg0.55
Layers from ground: thickness (m), average SPT N — last row is the bearing layer4, 3 5, 10 3, 18 4, 35

Worked example — results

ResultValueUnit
Perimeter1.60m
Base area0.160m²
Shaft factor2.00kPa per N
Pile length16.00m
N at toe (bearing layer)35.00
Embedment in bearing layer4.00m
qb = min(40N·Lb/D, 400N)14,000kPa
Base resistance2,240kN
Shaft resistance819.2kN
Ultimate Rug3,059kN
Design φg·Rug1,683kN
00.5limit 1.0φg·Rug ≥ E*0.53 PASS
Diagram for the worked example

Method, formulas and assumptions

Related foundations calculators

For preliminary design and education. Check every result against the current standard and your own engineering judgement before use.